What Size Wire for a 20 Amp Circuit Breaker? (NEC Table 310.16)

Complete Copper vs. Aluminum AWG wire size, continuous load limit (16A max), ground wire gauge, and conduit sizing for 20A circuits (Kitchen, bathroom, garage, commercial 20A receptacles & small appliances).

Direct NEC Table 310.16 Answer for 20 Amps

12 AWG
Minimum Copper Wire (75°C)
THHN / THWN-2 / XHHW in Conduit
10 AWG
Minimum Aluminum Wire (75°C)
SER / XHHW-2 Feeder Cable
16 Amps
Max Continuous Load (80% Rule)
For loads running 3+ hours (EVs, lighting)
1/2" EMT
Recommended Conduit Size
Fits 3x 12 AWG + Ground under 40% fill

Common Applications for a 20A Circuit

Kitchen, bathroom, garage, commercial 20A receptacles & small appliances. Remember that under the NEC 125% continuous-load rule (NEC 210.19 & 210.20), a standard 20A breaker can only supply up to 16A of continuous load (any load that runs for 3 hours or more without stopping, such as an EV charger or commercial lighting).

When to Upsize for Voltage Drop (Over 100 Feet)

If your one-way wire run exceeds 100 feet at 240V (or 50 feet at 120V), step up one wire gauge from 12 AWG to keep total line voltage drop under the NEC 3% branch-circuit recommendation. Use our Voltage Drop Calculator to check your exact footage.

2. NEC Wire Size & Ampacity Calculator (Table 310.16)