What Size Wire for a 40 Amp Circuit Breaker? (NEC Table 310.16)
Complete Copper vs. Aluminum AWG wire size, continuous load limit (32A max), ground wire gauge, and conduit sizing for 40A circuits (Electric ranges, cooktops & 32A continuous Level 2 EV chargers).
Direct NEC Table 310.16 Answer for 40 Amps
Common Applications for a 40A Circuit
Electric ranges, cooktops & 32A continuous Level 2 EV chargers. Remember that under the NEC 125% continuous-load rule (NEC 210.19 & 210.20), a standard 40A breaker can only supply up to 32A of continuous load (any load that runs for 3 hours or more without stopping, such as an EV charger or commercial lighting).
When to Upsize for Voltage Drop (Over 100 Feet)
If your one-way wire run exceeds 100 feet at 240V (or 50 feet at 120V), step up one wire gauge from 8 AWG to keep total line voltage drop under the NEC 3% branch-circuit recommendation. Use our Voltage Drop Calculator to check your exact footage.