How Many 10 AWG Wires Fit in 1/2" EMT Conduit?

Direct NEC Chapter 9 Table 4 & Table 5 calculation for 10 AWG conductors (30A water heater, dryer & A/C circuits) inside 1/2" EMT Conduit.

NEC Answer: 5 Conductors Maximum (10 AWG THHN at 40% Fill)

5 Wires
Max 10 AWG THHN / THWN-2
Standard Run (40% Fill = 0.122 sq in)
8 Wires
Conduit Nipple ≤ 24" (60% Fill)
NEC Chapter 9 Note 4 Nipple Allowance
5 Wires
Max 10 AWG XHHW / XHHW-2
40% Fill (0.0243 sq in per wire)
0.304 sq in
1/2" EMT Total Area
Internal Diameter: 0.622"
Insulation TypeSingle 10 AWG Area1 Wire (53% Fill)2 Wires (31% Fill)3+ Wires (40% Standard)Nipple ≤24" (60% Fill)
THHN / THWN-2 0.0211 sq in 0.161 sq in 0.094 sq in 5 wires (0.122 sq in) 8 wires (0.182 sq in)
XHHW / XHHW-2 0.0243 sq in 0.161 sq in 0.094 sq in 5 wires (0.122 sq in) 7 wires (0.182 sq in)

NEC Chapter 9 Derating Reminder for 5 Conductors

While 1/2" EMT Conduit physically and legally holds up to 5 10 AWG THHN wires under the 40% cross-sectional area rule, remember NEC Table 310.15(C)(1): whenever you place 4 to 6 current-carrying conductors in the same raceway, you must derate their 90°C ampacity to 80% (and to 70% for 7 to 9 current-carrying conductors).