How Many 2 AWG Wires Fit in 1" PVC Schedule 40 Conduit?

Direct NEC Chapter 9 Table 4 & Table 5 calculation for 2 AWG conductors (95A–115A subpanel & service entrance feeders) inside 1" PVC Schedule 40 Conduit.

NEC Answer: 2 Conductors Maximum (2 AWG THHN at 40% Fill)

2 Wires
Max 2 AWG THHN / THWN-2
Standard Run (40% Fill = 0.333 sq in)
4 Wires
Conduit Nipple ≤ 24" (60% Fill)
NEC Chapter 9 Note 4 Nipple Allowance
2 Wires
Max 2 AWG XHHW / XHHW-2
40% Fill (0.1146 sq in per wire)
0.832 sq in
1" PVC40 Total Area
Internal Diameter: 1.029"
Insulation TypeSingle 2 AWG Area1 Wire (53% Fill)2 Wires (31% Fill)3+ Wires (40% Standard)Nipple ≤24" (60% Fill)
THHN / THWN-2 0.1158 sq in 0.441 sq in 0.258 sq in 2 wires (0.333 sq in) 4 wires (0.499 sq in)
XHHW / XHHW-2 0.1146 sq in 0.441 sq in 0.258 sq in 2 wires (0.333 sq in) 4 wires (0.499 sq in)

NEC Chapter 9 Derating Reminder for 2 Conductors

While 1" PVC Schedule 40 Conduit physically and legally holds up to 2 2 AWG THHN wires under the 40% cross-sectional area rule, remember NEC Table 310.15(C)(1): whenever you place 4 to 6 current-carrying conductors in the same raceway, you must derate their 90°C ampacity to 80% (and to 70% for 7 to 9 current-carrying conductors).