How Many 3/0 AWG Wires Fit in 1-1/2" EMT Conduit?

Direct NEC Chapter 9 Table 4 & Table 5 calculation for 3/0 AWG conductors (200A copper service entrance & heavy feeders) inside 1-1/2" EMT Conduit.

NEC Answer: 3 Conductors Maximum (3/0 AWG THHN at 40% Fill)

3 Wires
Max 3/0 AWG THHN / THWN-2
Standard Run (40% Fill = 0.814 sq in)
4 Wires
Conduit Nipple ≤ 24" (60% Fill)
NEC Chapter 9 Note 4 Nipple Allowance
3 Wires
Max 3/0 AWG XHHW / XHHW-2
40% Fill (0.2642 sq in per wire)
2.036 sq in
1-1/2" EMT Total Area
Internal Diameter: 1.61"
Insulation TypeSingle 3/0 AWG Area1 Wire (53% Fill)2 Wires (31% Fill)3+ Wires (40% Standard)Nipple ≤24" (60% Fill)
THHN / THWN-2 0.2679 sq in 1.079 sq in 0.631 sq in 3 wires (0.814 sq in) 4 wires (1.222 sq in)
XHHW / XHHW-2 0.2642 sq in 1.079 sq in 0.631 sq in 3 wires (0.814 sq in) 4 wires (1.222 sq in)

NEC Chapter 9 Derating Reminder for 3 Conductors

While 1-1/2" EMT Conduit physically and legally holds up to 3 3/0 AWG THHN wires under the 40% cross-sectional area rule, remember NEC Table 310.15(C)(1): whenever you place 4 to 6 current-carrying conductors in the same raceway, you must derate their 90°C ampacity to 80% (and to 70% for 7 to 9 current-carrying conductors).