How Many 4 AWG Wires Fit in 1-1/4" PVC Schedule 40 Conduit?

Direct NEC Chapter 9 Table 4 & Table 5 calculation for 4 AWG conductors (70A–85A subpanel & commercial equipment feeders) inside 1-1/4" PVC Schedule 40 Conduit.

NEC Answer: 7 Conductors Maximum (4 AWG THHN at 40% Fill)

7 Wires
Max 4 AWG THHN / THWN-2
Standard Run (40% Fill = 0.581 sq in)
10 Wires
Conduit Nipple ≤ 24" (60% Fill)
NEC Chapter 9 Note 4 Nipple Allowance
7 Wires
Max 4 AWG XHHW / XHHW-2
40% Fill (0.0814 sq in per wire)
1.453 sq in
1-1/4" PVC40 Total Area
Internal Diameter: 1.36"
Insulation TypeSingle 4 AWG Area1 Wire (53% Fill)2 Wires (31% Fill)3+ Wires (40% Standard)Nipple ≤24" (60% Fill)
THHN / THWN-2 0.0824 sq in 0.770 sq in 0.450 sq in 7 wires (0.581 sq in) 10 wires (0.872 sq in)
XHHW / XHHW-2 0.0814 sq in 0.770 sq in 0.450 sq in 7 wires (0.581 sq in) 10 wires (0.872 sq in)

NEC Chapter 9 Derating Reminder for 7 Conductors

While 1-1/4" PVC Schedule 40 Conduit physically and legally holds up to 7 4 AWG THHN wires under the 40% cross-sectional area rule, remember NEC Table 310.15(C)(1): whenever you place 4 to 6 current-carrying conductors in the same raceway, you must derate their 90°C ampacity to 80% (and to 70% for 7 to 9 current-carrying conductors).

1. NEC Conduit Fill Calculator (Chapter 9, Tables 1, 4 & 5)

Recommended Job-Site Materials & Tools for This Run

Trade SizeInternal Dia.Total AreaBundle Fill %Max Primary WiresNEC Status