How Many 4 AWG Wires Fit in 2" EMT Conduit?

Direct NEC Chapter 9 Table 4 & Table 5 calculation for 4 AWG conductors (70A–85A subpanel & commercial equipment feeders) inside 2" EMT Conduit.

NEC Answer: 16 Conductors Maximum (4 AWG THHN at 40% Fill)

16 Wires
Max 4 AWG THHN / THWN-2
Standard Run (40% Fill = 1.342 sq in)
24 Wires
Conduit Nipple ≤ 24" (60% Fill)
NEC Chapter 9 Note 4 Nipple Allowance
16 Wires
Max 4 AWG XHHW / XHHW-2
40% Fill (0.0814 sq in per wire)
3.356 sq in
2" EMT Total Area
Internal Diameter: 2.067"
Insulation TypeSingle 4 AWG Area1 Wire (53% Fill)2 Wires (31% Fill)3+ Wires (40% Standard)Nipple ≤24" (60% Fill)
THHN / THWN-2 0.0824 sq in 1.779 sq in 1.040 sq in 16 wires (1.342 sq in) 24 wires (2.014 sq in)
XHHW / XHHW-2 0.0814 sq in 1.779 sq in 1.040 sq in 16 wires (1.342 sq in) 24 wires (2.014 sq in)

NEC Chapter 9 Derating Reminder for 16 Conductors

While 2" EMT Conduit physically and legally holds up to 16 4 AWG THHN wires under the 40% cross-sectional area rule, remember NEC Table 310.15(C)(1): whenever you place 4 to 6 current-carrying conductors in the same raceway, you must derate their 90°C ampacity to 80% (and to 70% for 7 to 9 current-carrying conductors).